I saw that you have a TOP Server Driver for the Modbus protocol, will this support JBus as well? If yes; Is there anything I should be aware of when configuring this in TOP Server?
The Modbus Protocol was initially developed by Modicon. April develeoped their own version of Modbus; later dubbed JBus. The two protocols are certainly compatible, and the TOP Server Modbus driver will be able to communicate with devices that speak either protocol.
There are a few considerations that need to be taken into account:
- Modbus is natively a 0 based addressing protocol (Reg+1), whereas JBus is natively a 1 based addressing protocol (Reg+0). The register offset of 1 can easily be configured in the device properties "Use zero based addressing" found under the Settings tab
- Modbus and JBus have different "limitations" when it comes to packet capacity
JBus | Modbus | |
Number of Stations on bus | 255 | 247 |
Max number of bits to be read in single request | 2000 | 1920 |
Max number of words to be read in single request | 125 | 120 |
Max number of bits to be writen in single request | 1968 | 1920 |
Max number of words to be written in single request | 123 | 120 |
This limitation must be taken into account when setting up the Block Settings of the TOP Server device - since Modbus is lower across the board there should not be any problems with JBus Devices.
If communicating with a JBus device and experiencing problems, please contact our technical support staff and we would be more than happy to assist